Create check-ups-runtime.sh

This commit is contained in:
Ssyleric
2025-11-03 17:03:23 +01:00
committed by GitHub
parent 38db399088
commit f182aff3d0

25
check-ups-runtime.sh Normal file
View File

@@ -0,0 +1,25 @@
#!/bin/bash
WEBHOOK="https://discord.com/api/webhooks/1234567890987654321/jsdkghfojahjgoaropihjgoirhjfsdighajsdfnbgkvjasznbfgousoghsoaghoasdhgjnsdfjnv;jsdfnvjfsdgnd"
LOGFILE="/var/log/ups-shutdown.log"
STATEFILE="/tmp/ups-runtime-alert.sent"
UPS_DATA=$(upsc eaton@localhost 2>/dev/null)
STATUS=$(echo "$UPS_DATA" | awk -F': ' '/^ups.status:/ {print $2}')
RUNTIME=$(echo "$UPS_DATA" | awk -F': ' '/^battery.runtime:/ {print $2}')
BATTERY_CHARGE=$(echo "$UPS_DATA" | awk -F': ' '/^battery.charge:/ {print $2}')
MODEL=$(echo "$UPS_DATA" | awk -F': ' '/^device.model:/ {print $2}')
# Si autonomie < 300 sec et que message pas encore envoyé
if [[ "$RUNTIME" -lt 300 ]]; then
if [[ ! -f "$STATEFILE" ]]; then
MESSAGE="⏱ *$(hostname)* — ⚠️ Autonomie critique UPS à $(date '+%F %T')\n🔋 Batterie : ${BATTERY_CHARGE} %\n⏳ Autonomie : ${RUNTIME} sec\n🖥 Modèle : ${MODEL}"
echo "$(date '+%F %T') 🚨 ALERTE: autonomie < 300 sec (batt=$BATTERY_CHARGE%, runtime=$RUNTIME sec)" >> "$LOGFILE"
jq -n --arg content "$MESSAGE" '{content: $content}' | \
curl -s -H "Content-Type: application/json" -X POST -d @- "$WEBHOOK" > /dev/null
touch "$STATEFILE"
fi
else
# Si autonomie > 300 sec, reset le flag dalerte
[[ -f "$STATEFILE" ]] && rm -f "$STATEFILE"
fi